Skip to content

Southwire 2-2-4 SEU Copper Cable

0 Reviews
SKU
2 SEU CU

Southwire 2-2-4 SEU Copper CableAdditional specifications Additional specifications · Electrical Inductive reactance at 60 Hz 0.045 Ω/1000 ft AC resistance at 75°C 0.201 Ω/1000 ft Voltage rating 600 V DC resistance at 25°C 0.162 Ω/1000 ft Additional specifications · Compliance Referenced UL standards UL 44, UL 83, and UL 854 Electrical co...

Needs Data

Product Overview

Southwire 2-2-4 SEU Copper Cable

Additional specifications

Additional specifications · Electrical

Inductive reactance at 60 Hz 0.045 Ω/1000 ft
AC resistance at 75°C 0.201 Ω/1000 ft
Voltage rating 600 V
DC resistance at 25°C 0.162 Ω/1000 ft

Additional specifications · Compliance

Referenced UL standards UL 44, UL 83, and UL 854
Electrical code reference NEC National Electrical Code NFPA 70
Federal specification A-A-59544
Conductor standards ASTM B3 and ASTM B8
RoHS-2 and CE marking scope RoHS-2 (European Directive 2011/65/EU); CE marking applies only to RoHS-2 material restrictions

Additional specifications · Construction

Jacket thickness 30 mil
Conductor construction Class B compressed stranded
Individual conductor insulation Cross Linked Polyethylene (XLPE) Type XHHW-2 or Polyvinyl Chloride with Nylon Sheath THHN/THWN
Neutral construction Insulated bare soft annealed neutral
Jacket material Polyvinyl Chloride (PVC)
Sunlight resistance Jacket and individual conductors are sunlight resistant
Binder Reinforcement binder
Conductor stranding count 7 strands
Insulation thickness 45 mil

Additional specifications · Installation

Maximum pull tension 1061 lb
Minimum bend radius 3.9 in
Underground installation Not permitted underground, with or without a raceway

Additional specifications · Operating Conditions

Permitted locations Wet or dry locations
Maximum operating temperature 90 °C

Additional specifications · Applications

Application and compatibility Primarily from the service drop to the meter base and from the meter base to the distribution panelboard; also usable where Type SE cable is permitted

Technical Specifications

Product information and specifications for the selected item.

SKU: 2 SEU CU

Product Information

BrandSouthwire
MPN2 SEU CU
SKU2 SEU CU
CategoryService Entrance Cable

Key Specs

Maximum Amperage (A)130
Wire Gauge2/4
Conductor MaterialCopper
Cable/Wire TypeSEU
Total Wire Length (ft.)500

Ratings & Conductor

Maximum Amperage (A)130
Wire Gauge2/4
Conductor MaterialCopper
Cable/Wire TypeSEU
Inductive reactance at 60 Hz0.045 Ω/1000 ft
Referenced UL standardsUL 44, UL 83, and UL 854
Electrical code referenceNEC National Electrical Code NFPA 70
Conductor constructionClass B compressed stranded
Individual conductor insulationCross Linked Polyethylene (XLPE) Type XHHW-2 or Polyvinyl Chloride with Nylon Sheath THHN/THWN
Federal specificationA-A-59544
Maximum operating temperature90 °C
Neutral constructionInsulated bare soft annealed neutral
AC resistance at 75°C0.201 Ω/1000 ft
Conductor standardsASTM B3 and ASTM B8
Voltage rating600 V
DC resistance at 25°C0.162 Ω/1000 ft
RoHS-2 and CE marking scopeRoHS-2 (European Directive 2011/65/EU); CE marking applies only to RoHS-2 material restrictions
Conductor stranding count7 strands
Insulation thickness45 mil

Cable Details

Total Wire Length (ft.)500
Wire Cut TypeCut By-The-Foot
Jacket ColorGray
Jacket thickness30 mil
Maximum pull tension1061 lb
Permitted locationsWet or dry locations
Jacket materialPolyvinyl Chloride (PVC)
Application and compatibilityPrimarily from the service drop to the meter base and from the meter base to the distribution panelboard; also usable where Type SE cable is permitted
Sunlight resistanceJacket and individual conductors are sunlight resistant
BinderReinforcement binder
Minimum bend radius3.9 in
Underground installationNot permitted underground, with or without a raceway

Dimensions & Weight

Height (in.)0.587
Width (in.)0.964
Length (in.)6000