Skip to content

Eaton CCV 150A Tenant Main Circuit Breaker, 2-Pole, 120/240V

0 Reviews
SKU
CCV2150X

The Eaton CCV2150X is a 150 A, 2-pole tenant-main circuit breaker rated 120/240 V AC with a 10 kAIC interrupting rating. It uses bolt-on mounting and load-side terminals only, and is compatible with Type ECC unit enclosures and specified Eaton metering systems.

  • 150 A, 2-Pole Main Breaker
  • 120/240 V AC Rating
  • 10 kAIC Interrupting Rating
  • Metering-System and Enclosure Compatibility
  • Load-Side Terminal Configuration
  • Bolt-On Mounting

Product Overview

The Eaton CCV2150X is a 150 A, 2-pole tenant-main circuit breaker rated 120/240 V AC with a 10 kAIC interrupting rating. It uses bolt-on mounting and load-side terminals only, and is compatible with Type ECC unit enclosures and specified Eaton metering systems.

Technical Specifications

Product information and specifications for the selected item.

SKU: CCV2150X

Product Information

BrandEaton
MPNCCV2150X
SKUCCV2150X
UPC / GTIN786685368467
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)150
Voltage120/240 V AC
Interruption TypeStandard Trip
Breaker TypeMain Breaker
Mounting TypeBolt-On

Electrical Ratings

Maximum Amperage (A)150
Voltage120/240 V AC
Interruption TypeStandard Trip
Calibration temperature40 °C
Conductor size and temperature rating#2/0–300 kcmil Cu/Al; 60°C or 75°C
Factory calibrationCalibrated and sealed after assembly
Wire size and temperature rating#2/0–300 kcmil Cu/Al; 60°C or 75°C

Breaker Configuration

Breaker TypeMain Breaker
Mounting TypeBolt-On
Series TypeCCV
Compatible metering systems1MP meter packs, 1MM residential meter stacks, and 3MM three-phase-in/single-phase-out meter stacks
Terminal lug compatibilityStandard wire-connector lugs suitable for copper or aluminum wire
Compatible metering stacks35MM and 35SS single-phase modular metering stacks
Handle and reset behaviorTrip-free handle with ON-TRIPPED-OFF positions; reset past OFF to latch contacts after tripping
Compatible enclosuresType ECC Unit Enclosures
Terminal-side configurationLoad-side terminals
Trip element constructionIndirectly heated bimetal elements; calibrated and sealed after assembly
Backward compatibilitySame profile and footprint as CC/CCH breakers, allowing use in the same applications
Lug type and conductor compatibilityStandard lugs suitable for copper or aluminum wire

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsUL Listed
WarrantyLimited lifetime residential; 1 year commercial

Dimensions & Weight

Height (in.)5.5
Width (in.)4.5
Length (in.)8
Weight (lb.)2.83

Product Documents